Toroidal abrible IAM 1000/5
P&P0787Transformadores abribles de medida 1000/5
Documents
Technical guide
Compatibility and configuration
Official data for Celsa IAM 1000/5: 1,000/5 A split-core current transformer
Reference
IAM 1000/5
Current
Primario 1.000 A · secundario 5 A
Window
4 × 80 × 10 mm o cable Ø80 mm
Range
50-60 Hz
Voltage
Red hasta 720 V
Insulation
3 kV · 50 Hz · 1 min
Classes
0,5 / 1 / 3
Burden at 1,000 A
10 / 20 / 45 VA
Application
Indoor low-voltage metering
Technical frequently asked questions
What is its function?
It converts a 1,000 A primary current to a 5 A signal.
Which system is it compatible with?
Use it with meters compatible with a 5 A secondary.
What must be checked before installation?
Do not open the secondary under load; check polarity, class and window.
Official sources published on this product page: data sheet. Specifications are subject to the conditions in the linked documents. The source does not publish an unambiguous total weight for this item, so structured weight is omitted.